CAD (0)
▾
5.7" VGA HMI plus Control with digital output sink type, 262K Colors
Unit of Measure
Display Specifications
|
Interface Specifications
|
Specifications
|
Electrical Specifications
|
Environmental Specifications
|
Structural Specifications
Display Specifications
Type |
N/A TFT Color LCD (VGA) |
Size |
N/A 5.7" |
Colors |
N/A 262,144 |
Resolution |
N/A 640 x 480 pixels |
Brightness Adjustment |
N/A 16 levels of adjustment available via touch panel in the Configuration menu |
Backlight |
N/A White LED adjustable on/off control |
Area |
N/A 95.04 x 53.86 mm (3.74 x 2.12 in) |
Touch Panel |
N/A Resistive Film (Analog) 1024 x 1024 pixels |
Backup |
N/A Uses a part of Flash EPROM as the backup area. (Maximum usable capacity*1: 392 KB) |
System |
N/A Flash EPROM 1 GB (operating system, project data and other data) |
Interface Specifications
Serial (COM1) |
N/A RS-232C/422/485 |
Ethernet |
N/A IEEE802.3i/IEEE802.3u, 10BASE-T/100BASE-TX, Modular jack (RJ-45) x 1 |
USB |
N/A USB 2.0 (Type A) x 1 , USB 2.0 (micro-B) x 1 |
CANOpen |
N/A Reserved |
Specifications
Built in DIO (Input) |
N/A 24 Vdc open collector. Single phase (4-point) 2 phase (1-point or 2-point) |
Built in DIO (Output) |
N/A 4 points |
Clock |
N/A Battery backed clock. |
Electrical Specifications
Rated Voltage |
N/A 24 Vdc |
Rated Voltage Range |
N/A 20.4 Vdc to 28.8 Vdc |
Power Consumption |
N/A Max 11.3 W |
Environmental Specifications
Minimal Ambiant Operating Temperature |
N/A 0 ºC32 ºF |
Maximal Ambiant Operating Temperature |
N/A 50 ºC122 ºF |
Storage Temperature |
N/A -20 to 60 ºC-4 to 140 ºF |
Dust |
N/A 0.1 mg/m3 (10-7 oz/ft3) or less (non-conductive levels) |
Pollution Degree |
N/A For use in Pollution Degree 2 environment. |
Corrosive Gases |
N/A Free of corrosive gases |
Vibration & Shock Resistance |
N/A IEC/EN 61131-2 compliant, 5...9 Hz Single amplitude 3.5 mm (0.14 in) 9...150 Hz Fixed acceleration: 9.8 m/s2 X, Y, Z directions for 10 cycles (approximately 100 minutes) |
Shock Resistance |
N/A IEC/EN 61131-2 compliant 147 m/s2, X, Y, Z directions for 3 times |
Structural Specifications
| Ratings1 | N/A IP65F, UL 50/50E, Type 1, Type 4X (indoor use only), Type 12 and Type 13 (on the front panel when properly installed in an enclosure) |
Certifications |
N/A UL 61010-2-201 and CSA C22.2 N°61010-2-201, for Industrial Control Equipment used in Ordinary Locations, Underwriters Laboratories Inc., UL 121201 and CSA C22.2 N°213, for Industrial Control Equipment used in Class I, Division 2 Hazardous (Classified) Loc |
Cooling method |
N/A Natural Air Circulation |
External Length |
N/A 6.67 in169.5 mm |
External Depth |
N/A 2.36 in60 mm |
External Height |
N/A 5.39 in137 mm |
Panel Cut Length |
N/A 6.14 in156 mm |
Panel Cut Height |
N/A 4.86 in123.5 mm |
| Panel Thickness Area2 | N/A 0.06 to 0.2 in1.6 to 5 mm |
Warranty |
N/A 18 Month Standard |
Weight |
N/A 0.8 kg1.76 lb |
- 1 The front face of this product, installed in a solid panel, has been tested using conditions equivalent to the standards shown in the specification. Even though this product's level of resistance is equivalent to these standards, oils that should have no effect on this product can possibly harm this product. This can occur in areas where either vaporized oils are present, or where low viscosity cutting oils are allowed to adhere to this product for long periods of time. If this product's front face protection sheet or cover glass peels off, these conditions can lead to the ingress of oil into this product and separate protection measures are suggested. Also, if non-approved oils are present, they may cause deformation or corrosion of the front panel's cover. Therefore, prior to installing this product, be sure to confirm the type of conditions that will be present in this product's operating environment. If the installation gasket is used for a long period of time, or if this product and its gasket are removed from the panel, the original level of protection cannot be kept. To maintain the original protection level, be sure to replace the installation gasket regularly.
- 2 Even if the installation wall thickness is within the recommended range for the Panel Cut Dimensions, depending on the wall's material, size, and installation. location of this product and other devices, the installation wall could warp. To prevent warping, the installation surface may need to be strengthened.(R0.12 in).