Electrical Specifications
|
Environmental Specifications
|
Structural Specifications
|
Functional Specifications
|
Specifications
Electrical Specifications
Rated Input Voltage |
N/A 24 Vdc |
Input voltage limits |
N/A 19.2 to 28.8 V |
Voltage drop |
N/A 5 ms or less |
Power Consumption |
N/A 11 W |
In-rush current |
N/A 30 A or less |
Voltage endurance |
N/A 1,000 Vac, 20 mA for 1 minute (between charging and FG terminals) |
Insulation resistance |
N/A 500 Vdc, 10 MO or more (between charging and FG terminals) |
Environmental Specifications
Minimal Surrounding Air Temperature |
N/A 0 ºC32 ºF |
Maximal Surrounding Air Temperature |
N/A 60 ºC140 ºF |
Storage Temperature |
N/A -20 to 60 ºC-4 to 140 ºF |
Surrounding air and storage humidity |
N/A 10%...90% RH (Non condensing, wet bulb temperature 39 ºC [102.2 ºF] or less) |
Dust |
N/A 0.1 mg/m3 (10-7 oz/ft3) or less (non-conductive levels) |
Pollution degree |
N/A For use in Pollution Degree 2 environment |
Corrosive gases |
N/A Free of corrosive gases |
Atmospheric pressure (operating altitude) |
N/A 800...1,114 hPa (2,000 m [6,561 ft] or lower) |
Vibration resistance |
N/A IEC/EN 61131-2 compliant 5...9 Hz Single amplitude 3.5 mm (0.14 in) 9...150 Hz Fixed acceleration: 9.8 m/s2 X, Y, Z directions for 10 cycles (approximately 100 minutes) |
Shock resistance |
N/A IEC/EN 61131-2 compliant 147 m/s2, X, Y, Z directions for 3 times |
Noise immunity |
N/A Noise voltage: 1,000 Vp-p Pulse duration: 1 µs Rise time: 1 ns (via noise simulator) |
Electrostatic discharge immunity |
N/A Contact discharge method: 6 kV Air discharge method: 8 kV (IEC/EN 61000-4-2 Level 3) |
Structural Specifications
Grounding |
N/A Functional grounding: Grounding resistance of 100 O, 2 mm2 (AWG 14) or thicker wire, or your country's applicable standard (same for FG and SG terminals). |
Cooling method |
N/A Natural Air Circulation |
Structure |
N/A Rating: Equivalent to IP20 Installation configuration: 35 mm (1.38 in) DIN rail or panel mounted (IEC 60715 compliant) |
External Length |
N/A 4.96 in126 mm |
External Depth |
N/A 1.81 in46 mm |
External Height |
N/A 6.38 in162 mm |
Weight |
N/A 0.7 kg1.54 lb |